3-PAGE VECTOR A4 STUDIO
EPA 40 CFR Part 84 & Section 608 Quick Reference Summary Citation: 40 CFR Part 84, Subpart C (AIM Act >= 15 lbs)

Commercial Walk-In Cooler (Medium-Temp) (R-410A): Factory Charge Spec, PT Chart & QR Rooftop Tag Studio

For a Commercial Walk-In Cooler (Medium-Temp) charged with 18 lbs 8 oz (18.50 lbs) of R-410A (GWP 2088, ASHRAE Class A1), the 2026 EPA 40 CFR Part 84 maximum leak rate threshold is 20% (Commercial Refrigeration (20% Max EPA Leak Rate)). Adding more than 3 lbs 11 oz (3.70 lbs) in 12 months (Rolling Average) or 0 lbs 15 oz (0.91 lbs) within 90 days (Annualizing) triggers a mandatory 30-day repair clock and 10-day follow-up verification test.

Exact R-410A Addition Weights That Trigger a 30-Day EPA Repair on a Commercial Walk-In Cooler (Medium-Temp)

Pre-computed for a nominal factory full charge of 18 lbs 8 oz under the 20% Commercial Refrigeration (20% Max EPA Leak Rate) limit:

Days Since Last Charge Annualizing Multiplier Max Addition Before 20% Trigger (Annualizing) Max 12-Mo Addition (Rolling Avg) 125% Chronic Leaker EPA Report Limit
30 Days 12.17x 0 lbs 5 oz (0.30 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)
60 Days 6.08x 0 lbs 10 oz (0.61 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)
90 Days 4.06x 0 lbs 15 oz (0.91 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)
180 Days 2.03x 1 lbs 13 oz (1.82 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)
270 Days 1.35x 2 lbs 12 oz (2.74 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)
365 Days 1.00x 3 lbs 11 oz (3.70 lbs) 3 lbs 11 oz (3.70 lbs) 23 lbs 2 oz (23.13 lbs)

R-410A (Puron / Genetron AZ-20) Thermodynamic & Safety Profile

Global Warming Potential
2088 (AR4 100-Yr)
ASHRAE 34 Safety Class
Non-Flammable (ASHRAE Class A1)
Charging Phase & Glide
Liquid Only (from inverted cylinder or dip tube) (0.3 degF Glide)
Lubricant & Thread Spec
POE (Polyolester Synthetic Oil) • Standard 1/4-inch Right-Hand Flare (RH)

R-410A Saturation Pressure-Temperature (PT) Reference (PSIG)

-10 degF 36.5 PSIG
0 degF 48.3 PSIG
20 degF 78.3 PSIG
40 degF 118.9 PSIG
60 degF 170.7 PSIG
85 degF 254.6 PSIG
105 degF 340.5 PSIG
125 degF 445.9 PSIG

R-410A DOT Recovery Cylinder 80% Maximum Safe Fill Weights (at 130 degF)

DOT Cylinder Specification Water Capacity (WC) Typical Tare Wt R-410A SG @ 130 degF Max 80% Net R-410A Charge Max Safe Gross Scale Reading
30-lb DOT-4BA400 Refrigerant Recovery Cylinder 26.2 lbs 17.8 lbs 0.91 19 lbs 1 oz (19.07 lbs) 36 lbs 14 oz (36.87 lbs)
50-lb DOT-4BA400 Refrigerant Recovery Cylinder 47.6 lbs 28.5 lbs 0.91 34 lbs 10 oz (34.65 lbs) 63 lbs 2 oz (63.15 lbs)
125-lb DOT-4BW400 Commercial Recovery Cylinder 123.0 lbs 62.0 lbs 0.91 89 lbs 9 oz (89.54 lbs) 151 lbs 9 oz (151.54 lbs)

Engineering & EPA Part 84 Field Compliance Protocol for R-410A Commercial Walk-In Cooler (Medium-Temp)

Under the US EPA AIM Act Subsection (h) rule (40 CFR Part 84, Subpart C) effective January 1, 2026, any Commercial Walk-In Cooler (Medium-Temp) operating with R-410A (Puron / Genetron AZ-20, AR4 GWP 2088) holding 15.0 pounds or more of refrigerant is subject to mandatory federal leak rate calculations and 3-year recordkeeping. With a nominal factory charge of 18 lbs 8 oz (18.50 lbs), this Walk-In Cooler Box exceeds the 15-pound threshold by 3.5 lbs and falls under the 20% maximum annual leak rate limit for Commercial Refrigeration (20% Max EPA Leak Rate).

SAFETY & OIL COMPATIBILITY: R-410A carries an ASHRAE Class A1 non-flammable classification and utilizes Standard 1/4-inch Right-Hand Flare (RH) service connections. This system circulates POE (Polyolester Synthetic Oil), which is highly hygroscopic in POE applications—requiring evacuation verification below 500 microns using an electronic thermistor or capacitance micron gauge prior to recharging.

CHARGING & PINPOINT VERIFICATION: With a negligible glide of 0.3 degF and a normal boiling point of -60.8 degF, R-410A maintains stable saturation pressures (118.9 PSIG at 40 degF evaporator coil; 340.5 PSIG at 105 degF condensing temperature). During EPA initial and follow-up verification tests, inspect Schrader service valve cores, brazed TXV distributor joints, high-pressure switch flare nuts, and microchannel condenser header bends..

Frequently Asked Questions: R-410A Walk-In Cooler Box Compliance

How many pounds or ounces of R-410A trigger an EPA leak repair on a Commercial Walk-In Cooler (Medium-Temp)?

For a Commercial Walk-In Cooler (Medium-Temp) holding 18 lbs 8 oz (18.50 lbs) of R-410A under the 20% Commercial Refrigeration (20% Max EPA Leak Rate) limit, adding more than 3 lbs 11 oz (3.70 lbs) over a rolling 365-day period triggers the mandatory 30-day EPA repair clock. Under the Annualizing Method, if only 90 days have elapsed since the last charge, adding just 0 lbs 15 oz (0.91 lbs) will exceed the 20% annualized threshold.

Is a Commercial Walk-In Cooler (Medium-Temp) using R-410A regulated under the 2026 EPA AIM Act 15-pound rule?

Yes. Because R-410A has a GWP of 2088 (greater than 53) and this Walk-In Cooler Box holds 18 lbs 8 oz (18.50 lbs) (at or above the 15-pound threshold effective January 1, 2026 under 40 CFR Part 84), the building owner and servicing contractor must calculate leak rates on every addition, perform initial and 10-day follow-up verification tests, and keep records for 3 years.

What triggers a mandatory EPA Chronic Leaker Report for this R-410A Walk-In Cooler Box?

Under 40 CFR 84.106(j), if cumulative refrigerant additions to this 18 lbs 8 oz (18.50 lbs) Walk-In Cooler Box reach or exceed 125% of its full charge (23 lbs 2 oz (23.13 lbs)) within a single calendar year, the owner/operator must submit a Chronic Leaker Report to the EPA by March 1 of the following year describing the root cause and corrective plan.