3-PAGE VECTOR A4 STUDIO
EPA 40 CFR Part 84 & Section 608 Quick Reference Summary Citation: 40 CFR Part 84, Subpart C (AIM Act >= 15 lbs)

Printable R-134a 7.5-Ton Packaged Rooftop Unit (RTU) EPA Compliance Log Sheet & Verification Certificate

For a 7.5-Ton Packaged Rooftop Unit (RTU) charged with 22 lbs 8 oz (22.50 lbs) of R-134a (GWP 1430, ASHRAE Class A1), the 2026 EPA 40 CFR Part 84 maximum leak rate threshold is 10% (Comfort Cooling (10% Max EPA Leak Rate)). Adding more than 2 lbs 4 oz (2.25 lbs) in 12 months (Rolling Average) or 0 lbs 9 oz (0.55 lbs) within 90 days (Annualizing) triggers a mandatory 30-day repair clock and 10-day follow-up verification test.

Exact R-134a Addition Weights That Trigger a 30-Day EPA Repair on a 7.5-Ton Packaged Rooftop Unit (RTU)

Pre-computed for a nominal factory full charge of 22 lbs 8 oz under the 10% Comfort Cooling (10% Max EPA Leak Rate) limit:

Days Since Last Charge Annualizing Multiplier Max Addition Before 10% Trigger (Annualizing) Max 12-Mo Addition (Rolling Avg) 125% Chronic Leaker EPA Report Limit
30 Days 12.17x 0 lbs 3 oz (0.18 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)
60 Days 6.08x 0 lbs 6 oz (0.37 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)
90 Days 4.06x 0 lbs 9 oz (0.55 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)
180 Days 2.03x 1 lbs 2 oz (1.11 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)
270 Days 1.35x 1 lbs 11 oz (1.66 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)
365 Days 1.00x 2 lbs 4 oz (2.25 lbs) 2 lbs 4 oz (2.25 lbs) 28 lbs 2 oz (28.13 lbs)

R-134a (Suva 134a / Genetron 134a) Thermodynamic & Safety Profile

Global Warming Potential
1430 (AR4 100-Yr)
ASHRAE 34 Safety Class
Non-Flammable (ASHRAE Class A1)
Charging Phase & Glide
Liquid or Vapor (Single-Component Zero Glide) (0 degF Glide)
Lubricant & Thread Spec
POE (Polyolester Synthetic Oil) • Standard 1/4-inch Right-Hand Flare (RH)

R-134a Saturation Pressure-Temperature (PT) Reference (PSIG)

-10 degF 1.9 PSIG
0 degF 6.5 PSIG
20 degF 18.4 PSIG
40 degF 35 PSIG
60 degF 57.4 PSIG
85 degF 95.2 PSIG
105 degF 135 PSIG
125 degF 184.6 PSIG

R-134a DOT Recovery Cylinder 80% Maximum Safe Fill Weights (at 130 degF)

DOT Cylinder Specification Water Capacity (WC) Typical Tare Wt R-134a SG @ 130 degF Max 80% Net R-134a Charge Max Safe Gross Scale Reading
30-lb DOT-4BA400 Refrigerant Recovery Cylinder 26.2 lbs 17.8 lbs 1.07 22 lbs 7 oz (22.43 lbs) 40 lbs 4 oz (40.23 lbs)
50-lb DOT-4BA400 Refrigerant Recovery Cylinder 47.6 lbs 28.5 lbs 1.07 40 lbs 12 oz (40.75 lbs) 69 lbs 4 oz (69.25 lbs)
125-lb DOT-4BW400 Commercial Recovery Cylinder 123.0 lbs 62.0 lbs 1.07 105 lbs 5 oz (105.29 lbs) 167 lbs 5 oz (167.29 lbs)

Engineering & EPA Part 84 Field Compliance Protocol for R-134a 7.5-Ton Packaged Rooftop Unit (RTU)

Under the US EPA AIM Act Subsection (h) rule (40 CFR Part 84, Subpart C) effective January 1, 2026, any 7.5-Ton Packaged Rooftop Unit (RTU) operating with R-134a (Suva 134a / Genetron 134a, AR4 GWP 1430) holding 15.0 pounds or more of refrigerant is subject to mandatory federal leak rate calculations and 3-year recordkeeping. With a nominal factory charge of 22 lbs 8 oz (22.50 lbs), this 7.5-Ton Packaged RTU exceeds the 15-pound threshold by 7.5 lbs and falls under the 10% maximum annual leak rate limit for Comfort Cooling (10% Max EPA Leak Rate).

SAFETY & OIL COMPATIBILITY: R-134a carries an ASHRAE Class A1 non-flammable classification and utilizes Standard 1/4-inch Right-Hand Flare (RH) service connections. This system circulates POE (Polyolester Synthetic Oil), which is highly hygroscopic in POE applications—requiring evacuation verification below 500 microns using an electronic thermistor or capacitance micron gauge prior to recharging.

CHARGING & PINPOINT VERIFICATION: With a negligible glide of 0 degF and a normal boiling point of -14.9 degF, R-134a maintains stable saturation pressures (35 PSIG at 40 degF evaporator coil; 135 PSIG at 105 degF condensing temperature). During EPA initial and follow-up verification tests, inspect Centrifugal and screw chiller shaft seals, relief valve rupture discs, and walk-in medium-temp evaporator flare fittings..

Frequently Asked Questions: R-134a 7.5-Ton Packaged RTU Compliance

How many pounds or ounces of R-134a trigger an EPA leak repair on a 7.5-Ton Packaged Rooftop Unit (RTU)?

For a 7.5-Ton Packaged Rooftop Unit (RTU) holding 22 lbs 8 oz (22.50 lbs) of R-134a under the 10% Comfort Cooling (10% Max EPA Leak Rate) limit, adding more than 2 lbs 4 oz (2.25 lbs) over a rolling 365-day period triggers the mandatory 30-day EPA repair clock. Under the Annualizing Method, if only 90 days have elapsed since the last charge, adding just 0 lbs 9 oz (0.55 lbs) will exceed the 10% annualized threshold.

Is a 7.5-Ton Packaged Rooftop Unit (RTU) using R-134a regulated under the 2026 EPA AIM Act 15-pound rule?

Yes. Because R-134a has a GWP of 1430 (greater than 53) and this 7.5-Ton Packaged RTU holds 22 lbs 8 oz (22.50 lbs) (at or above the 15-pound threshold effective January 1, 2026 under 40 CFR Part 84), the building owner and servicing contractor must calculate leak rates on every addition, perform initial and 10-day follow-up verification tests, and keep records for 3 years.

What triggers a mandatory EPA Chronic Leaker Report for this R-134a 7.5-Ton Packaged RTU?

Under 40 CFR 84.106(j), if cumulative refrigerant additions to this 22 lbs 8 oz (22.50 lbs) 7.5-Ton Packaged RTU reach or exceed 125% of its full charge (28 lbs 2 oz (28.13 lbs)) within a single calendar year, the owner/operator must submit a Chronic Leaker Report to the EPA by March 1 of the following year describing the root cause and corrective plan.