3-PAGE VECTOR A4 STUDIO
EPA 40 CFR Part 84 & Section 608 Quick Reference Summary Citation: 40 CFR Part 84, Subpart C (AIM Act >= 15 lbs)

Printable R-448A 10-Ton Dual-Circuit Commercial RTU EPA Compliance Log Sheet & Verification Certificate

For a 10-Ton Dual-Circuit Commercial RTU charged with 31 lbs 0 oz (31.00 lbs) of R-448A (GWP 1387, ASHRAE Class A1), the 2026 EPA 40 CFR Part 84 maximum leak rate threshold is 10% (Comfort Cooling (10% Max EPA Leak Rate)). Adding more than 3 lbs 2 oz (3.10 lbs) in 12 months (Rolling Average) or 0 lbs 12 oz (0.76 lbs) within 90 days (Annualizing) triggers a mandatory 30-day repair clock and 10-day follow-up verification test.

Exact R-448A Addition Weights That Trigger a 30-Day EPA Repair on a 10-Ton Dual-Circuit Commercial RTU

Pre-computed for a nominal factory full charge of 31 lbs 0 oz under the 10% Comfort Cooling (10% Max EPA Leak Rate) limit:

Days Since Last Charge Annualizing Multiplier Max Addition Before 10% Trigger (Annualizing) Max 12-Mo Addition (Rolling Avg) 125% Chronic Leaker EPA Report Limit
30 Days 12.17x 0 lbs 4 oz (0.25 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)
60 Days 6.08x 0 lbs 8 oz (0.51 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)
90 Days 4.06x 0 lbs 12 oz (0.76 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)
180 Days 2.03x 1 lbs 8 oz (1.53 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)
270 Days 1.35x 2 lbs 5 oz (2.29 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)
365 Days 1.00x 3 lbs 2 oz (3.10 lbs) 3 lbs 2 oz (3.10 lbs) 38 lbs 12 oz (38.75 lbs)

R-448A (Solstice N40) Thermodynamic & Safety Profile

Global Warming Potential
1387 (AR4 100-Yr)
ASHRAE 34 Safety Class
Non-Flammable (ASHRAE Class A1 High-Glide Retrofit Blend)
Charging Phase & Glide
Liquid Only (Mandatory — High 8.0 degF Temperature Glide) (8 degF Glide)
Lubricant & Thread Spec
POE (Polyolester Synthetic Oil) • Standard 1/4-inch Right-Hand Flare (RH)

R-448A Saturation Pressure-Temperature (PT) Reference (PSIG)

-10 degF 21.8 PSIG
0 degF 30.9 PSIG
20 degF 54.4 PSIG
40 degF 86.8 PSIG
60 degF 129.8 PSIG
85 degF 201.4 PSIG
105 degF 276.6 PSIG
125 degF 369.5 PSIG

R-448A DOT Recovery Cylinder 80% Maximum Safe Fill Weights (at 130 degF)

DOT Cylinder Specification Water Capacity (WC) Typical Tare Wt R-448A SG @ 130 degF Max 80% Net R-448A Charge Max Safe Gross Scale Reading
30-lb DOT-4BA400 Refrigerant Recovery Cylinder 26.2 lbs 17.8 lbs 0.89 18 lbs 10 oz (18.65 lbs) 36 lbs 7 oz (36.45 lbs)
50-lb DOT-4BA400 Refrigerant Recovery Cylinder 47.6 lbs 28.5 lbs 0.89 33 lbs 14 oz (33.89 lbs) 62 lbs 6 oz (62.39 lbs)
125-lb DOT-4BW400 Commercial Recovery Cylinder 123.0 lbs 62.0 lbs 0.89 87 lbs 9 oz (87.58 lbs) 149 lbs 9 oz (149.58 lbs)

Engineering & EPA Part 84 Field Compliance Protocol for R-448A 10-Ton Dual-Circuit Commercial RTU

Under the US EPA AIM Act Subsection (h) rule (40 CFR Part 84, Subpart C) effective January 1, 2026, any 10-Ton Dual-Circuit Commercial RTU operating with R-448A (Solstice N40, AR4 GWP 1387) holding 15.0 pounds or more of refrigerant is subject to mandatory federal leak rate calculations and 3-year recordkeeping. With a nominal factory charge of 31 lbs 0 oz (31.00 lbs), this 10-Ton Dual-Circuit RTU exceeds the 15-pound threshold by 16.0 lbs and falls under the 10% maximum annual leak rate limit for Comfort Cooling (10% Max EPA Leak Rate).

SAFETY & OIL COMPATIBILITY: R-448A carries an ASHRAE Class A1 non-flammable classification and utilizes Standard 1/4-inch Right-Hand Flare (RH) service connections. This system circulates POE (Polyolester Synthetic Oil), which is highly hygroscopic in POE applications—requiring evacuation verification below 500 microns using an electronic thermistor or capacitance micron gauge prior to recharging.

FRACTIONATION & GLIDE WARNING: R-448A is a zeotropic blend exhibiting a 8 degF temperature glide. If a leak occurs in a two-phase section of the 10-Ton Dual-Circuit RTU (such as Retrofitted R-404A/R-22 elastomers, Schrader valve O-rings, and supermarket rack oil separator float flanges.), the lower-boiling-point component vents preferentially, altering the remaining blend composition. Always charge R-448A strictly as Liquid Only (Mandatory — High 8.0 degF Temperature Glide) through a commercial throttling valve.

Frequently Asked Questions: R-448A 10-Ton Dual-Circuit RTU Compliance

How many pounds or ounces of R-448A trigger an EPA leak repair on a 10-Ton Dual-Circuit Commercial RTU?

For a 10-Ton Dual-Circuit Commercial RTU holding 31 lbs 0 oz (31.00 lbs) of R-448A under the 10% Comfort Cooling (10% Max EPA Leak Rate) limit, adding more than 3 lbs 2 oz (3.10 lbs) over a rolling 365-day period triggers the mandatory 30-day EPA repair clock. Under the Annualizing Method, if only 90 days have elapsed since the last charge, adding just 0 lbs 12 oz (0.76 lbs) will exceed the 10% annualized threshold.

Is a 10-Ton Dual-Circuit Commercial RTU using R-448A regulated under the 2026 EPA AIM Act 15-pound rule?

Yes. Because R-448A has a GWP of 1387 (greater than 53) and this 10-Ton Dual-Circuit RTU holds 31 lbs 0 oz (31.00 lbs) (at or above the 15-pound threshold effective January 1, 2026 under 40 CFR Part 84), the building owner and servicing contractor must calculate leak rates on every addition, perform initial and 10-day follow-up verification tests, and keep records for 3 years.

What triggers a mandatory EPA Chronic Leaker Report for this R-448A 10-Ton Dual-Circuit RTU?

Under 40 CFR 84.106(j), if cumulative refrigerant additions to this 31 lbs 0 oz (31.00 lbs) 10-Ton Dual-Circuit RTU reach or exceed 125% of its full charge (38 lbs 12 oz (38.75 lbs)) within a single calendar year, the owner/operator must submit a Chronic Leaker Report to the EPA by March 1 of the following year describing the root cause and corrective plan.